YQNT LC1-D AC Contactor is a 25A-class three-pole AC magnetic contactor designed for AC motor control, remote switching, and motor starter applications.
The contactor uses three main power poles and a normally open auxiliary contact for control or signaling circuits. It can be used as part of motor control assemblies with suitable thermal overload relays, auxiliary contacts and other control accessories.
For correct selection, check the motor current, main circuit voltage, utilization category, coil voltage, contact configuration, and operating conditions before ordering.
| Parameter | Specification |
|---|---|
| Product Type | AC Magnetic Contactor |
| Product Family | LC1-D |
| Rated Current Class | 25A |
| Main Pole Configuration | 3P / 3NO |
| Auxiliary Contact | 1NO |
| Application | AC Motor Control |
| Utilization Category | AC-3 for motor control |
| AC-3 Current Reference | 25A at 380V |
| Conventional Thermal Current Reference | 40A |
| Rated Insulation Voltage Reference | 660V |
| Motor Power Reference | 11kW at 380/400V AC-3 |
| Control Circuit | AC electromagnetic coil |
| Frequency | 50/60Hz, depending on coil version |
| Coil Voltage | Available according to the specified ordering configuration |
| Mounting | Confirm according to the selected product configuration |
| Accessories | Auxiliary contacts, thermal overload relay, mechanical interlock, and other compatible accessories |
| Brand | YQNT |
The LC1-D 25A contactor is a three-pole AC contactor.
The three main poles are used to switch the three-phase power circuit. The auxiliary contact is used for control, signaling or interlocking functions and should not be treated as a fourth main power pole.
Typical terminal identification is:
| Terminal | Function |
|---|---|
| 1/L1 – 2/T1 | Main power pole 1 |
| 3/L2 – 4/T2 | Main power pole 2 |
| 5/L3 – 6/T3 | Main power pole 3 |
| 13 – 14 | 1NO auxiliary contact |
This 3P + 1NO configuration is suitable for three-phase AC motor control and common motor starter control circuits.
If an application requires four independently switched main circuits, a four-pole contactor should be selected instead.
The LC1-D 25A class is intended for AC motor control under the applicable AC-3 operating conditions.
The related 25A contactor data provides the following reference values:
AC-3 rated current: 25A at 380V
Conventional thermal current: 40A
Rated insulation voltage: 660V
Motor power reference: 11kW at 380/400V AC-3
Motor power must not be selected from the ampere rating alone.
Before selecting the contactor, compare the contactor rating with the motor nameplate current, operating voltage, utilization category, and starting duty.
For applications involving frequent inching, plugging, reversing or other demanding switching conditions, the applicable utilization category should be checked before ordering.
Detailed Photos
Product Parameters

The contactor coil is part of the control circuit and should be selected according to the available control power supply.
The coil voltage is different from the main circuit voltage.
For example, a three-phase motor may operate from a higher power-circuit voltage while the contactor coil operates from a separate control voltage.
Available coil configurations should therefore be confirmed according to the exact product ordering code.
When requesting a quotation, specify:
Coil voltage
Coil frequency
Main circuit voltage
Motor rated current
Motor rated power
Required quantity
The product unit may carry a coil identification code. The exact coil voltage and frequency should be confirmed from the approved product configuration before shipment.
Contactor current ratings cannot be compared without considering the utilization category.
AC-1 is generally associated with non-inductive or lightly inductive loads, while AC-3 is used for typical squirrel-cage motor starting and switching applications.
AC-4 represents more demanding motor duties such as inching, plugging and frequent reversing.
Therefore, a contactor described as 25A should not automatically be treated as a 25A contactor for every load condition.
For motor applications, confirm:
Motor rated current
Motor operating voltage
Motor power
Utilization category
Starting and stopping frequency
Required electrical and mechanical endurance
This information allows the contactor to be selected according to the actual operating duty rather than the model number alone.
The LC1-D AC contactor is designed for applications involving remote switching and control of AC motor circuits.
Typical applications include:
Three-phase AC motor starting and stopping
Motor control panels
Electromagnetic motor starters
Motor control cabinets
Star-delta starter assemblies
Reversing and interlocking control
AC equipment control circuits
Motor starter assemblies with thermal overload protection
The contactor can be combined with suitable auxiliary contacts, thermal overload relays, mechanical interlocks and other control accessories to build a complete motor control system.
Accessory compatibility should be confirmed according to the selected contactor configuration.
A contactor controls the switching of the motor circuit. A thermal overload relay provides overload protection for the motor.
For a conventional motor starter assembly, the contactor and overload relay should be selected as a matched combination.
The selection should consider:
Motor full-load current
Contactor AC-3 rating
Overload relay adjustment range
Main circuit voltage
Coil voltage
Installation method
Required auxiliary contacts
YQNT can review the motor and control-circuit requirements to help identify the appropriate contactor and related protection components.
YQNT provides AC contactors for B2B electrical equipment buyers, distributors, panel builders and OEM customers.
For LC1-D contactor requirements, YQNT supports:
Product specification matching
Coil voltage and contact configuration confirmation
Technical documentation
OEM and private-label requirements
Product inspection requirements
Export packaging and documentation
Project-based product selection
For quotation, provide the required current, voltage, coil specification, contact configuration and quantity so the product configuration can be checked before order confirmation.
An LC1-D AC Contactor is an electromagnetic contactor used to switch and control AC electrical circuits, particularly AC motor circuits.
The 25A class is associated with a 25A AC-3 current reference under the applicable 380V conditions.
The standard configuration described on this page is a three-pole contactor with three main normally open power contacts.
No. The auxiliary contact is a control or signaling contact. It is not equivalent to a fourth main power pole.
The configuration described for this product is 1NO auxiliary contact.
The related 25A contactor data lists 11kW at 380/400V under AC-3 conditions. Final selection should be based on the motor rated current, voltage and actual operating duty.
Not necessarily. The coil voltage belongs to the control circuit, while the motor voltage belongs to the main power circuit. They should be specified separately.